Window 141 Flame Scanning System
The system includes three principal parts: the scanner head, the microcontroller module and the data terminal.Look at the running scanner
User's manual available upon request. Contact us for more details.System features and benefits
For the creation of the WINDOW 141 scanner, we applied our long field experience in flame scanning. We considered the following requirements and difficulties in the field:
| Discrimination problems (opposing and adjacent flames) | Independent UV and IR detection • Proven discrimination techniques • Detects IR flicker frequency up to 5000Hz |
| Scanner head alignment Flame behaviour |
• WINDOW type scanner head for sight adjustment and visual monitoring of the sighted flame to improve discrimination |
| Easy set point adjustment | • Individual adjustable FFRT from 0.5 to 3.5s (± 0.5) for both IR and UV • No adjusting potentiometers: adjustments are possible only by the handheld DT (Data Terminal) • Easy and comprehensive commissioning and adjusting procedures through Data Terminal |
| Application for various fuels | • Dual UV/IR detection with independent relay outputs |
| Comprehensive flame strength Comprehensive data analysis |
• Continuous display of relative and absolute values for both IR and UV |
| Reliable and safe system
|
• Complete fail safe operation system, UL1998 compliant • Safe output relays by dynamic operation • Mechanical shutter for continuous & efficient self-check • False flame signal detection • No backup battery required: settings stored permanently in flash memory • FM and CSA certified |
| Useful and standard connections | • Independent output and relays for UV and IR signals • 0 or 4 (selectable) to 20mA analog flame level output • Cooling air connection on scanner head • Plug-in module |
| Physical constraints | • Compact size of the scanner head • High temperatures resistant |
| Application for various types of installations | • Suitable on boilers, dryers, furnaces and kilns • For applications like power generation, coke (steel plants), ethanol production, chemical processes, refineries, methane tankers, pulp and paper plants, cement works |
| General features | • Multilayer, surface mount technology with flash memory microcontroller (RoHS standard) • No aperture disks or frequency filter necessary • Low power consumption (12-15VA max.) |